Avocent Worldwide
Avocent
Product Finder

PM10/20 NEMA models

The PM10/20 NEMA models use NEMA connectors for both power input and output. Distinct NEMA input connectors are used according to maximum current requirements. All NEMA outputs are NEMA5-15R rated receptacles. Twist-lock input plugs are available on many models.

All models come with two RS232 ports. One for management and one for daisy-chain connections. You can daisy-chain up to 128 power outlets that will behave as a single power management unit.

An LED display shows the current drawn by the unit in real time and you can be notified of an over current condition via a sound alarm or a console message. Also, if the unit is connected to a Cyclades console server or to an Avocent KVM switch, you can be notified via e-mail/SMS/SNMP. The NEMA models were designed to work on 100-125V environments and have the proper certificates to be safely deployed. Please see the table below for all available models.

                     Input Connection Max. input branch circuit rating Input Voltage Outlet current
Number of outlets
Form factor Approvals
NEMA Models
PM10-15A NEMA5-15P
15 amps
100-125
15 amps
10
Horizontal
FCC
Class A
CSA
PM10-20A NEMA5-20P
20 amps
100-125
15 amps
10
Horizontal
FCC
Class A
CSA
PM10-L20A NEMAL5-20P
20 amps
100-125
15 amps
10
Horizontal
FCC
Class A
CSA
PM10-L30A NEMAL5-30P
30 amps
100-125
15 amps
10
Horizontal
FCC
Class A
CSA
PM20-20A NEMA5-20P
20 amps
100-125
15 amps
20
Vertical
FCC
Class A
CSA
PM20-L20A NEMAL5-20P
20 amps
100-125
15 amps
20
Vertical
FCC
Class A
CSA
PM20-L30A NEMAL5-30P
30 amps
100-125
15 amps
20
Vertical
FCC
Class A
CSA