PM10/20 NEMA models
The PM10/20 NEMA models use NEMA connectors for both
power input and output. Distinct NEMA input connectors are used according to
maximum current requirements. All NEMA outputs are NEMA5-15R rated receptacles.
Twist-lock input plugs are available on many models.
All models come with two RS232 ports. One for management and
one for daisy-chain connections. You can daisy-chain up to 128 power outlets
that will behave as a single power management unit.
An LED display shows the current drawn by the unit in real
time and you can be notified of an over current condition via a sound alarm or a
console message. Also, if the unit is connected to a Cyclades console server or
to an Avocent KVM switch, you can be notified via e-mail/SMS/SNMP. The NEMA
models were designed to work on 100-125V environments and have the proper
certificates to be safely deployed. Please see the table below for all available
models.
|
Input Connection |
Max. input branch
circuit rating |
Input Voltage |
Outlet current |
Number of
outlets
|
Form factor |
Approvals |
| NEMA
Models |
|
PM10-15A |
NEMA5-15P |
15 amps
|
100-125
|
15 amps
|
10
|
Horizontal
|
FCC
Class A
CSA |
|
PM10-20A |
NEMA5-20P |
20 amps
|
100-125
|
15 amps
|
10
|
Horizontal
|
FCC
Class A
CSA |
|
PM10-L20A |
NEMAL5-20P |
20 amps
|
100-125
|
15 amps
|
10
|
Horizontal
|
FCC
Class A
CSA |
|
PM10-L30A |
NEMAL5-30P |
30 amps
|
100-125
|
15 amps
|
10
|
Horizontal
|
FCC
Class A
CSA |
|
PM20-20A
|
NEMA5-20P |
20 amps
|
100-125
|
15 amps
|
20
|
Vertical
|
FCC
Class A
CSA |
|
PM20-L20A |
NEMAL5-20P |
20 amps
|
100-125
|
15 amps
|
20
|
Vertical
|
FCC
Class A
CSA |
|
PM20-L30A |
NEMAL5-30P |
30 amps
|
100-125
|
15 amps
|
20
|
Vertical
|
FCC
Class A
CSA |
|

|